KVV - Copper core PVC insulated PVC sheathed control cable
Ideal for use in low-current control systems and environments with low-level electromagnetic interference.
Designed to ensure reliable performance in electrical control circuits, the KVV cable features polyvinyl chloride (PVC) material for both the internal conductor insulation and the outer sheath. This dual-layer PVC construction provides robust protection against moisture, physical wear, and chemical exposure. It is commonly applied in low-voltage power distribution networks as well as in signaling and monitoring loops.
Product structure diagram

Application
Designed for use in control, supervision, and protective circuitry where the AC rated voltage Uo/U does not exceed 450/750V.


Properties
Rated voltage Uo/U: 450/750V
Operating temperature limits:
Standard PVC-insulated types: maximum 70°C
Cross-linked polyethylene (XLPE) types: maximum 90°C
Minimum ambient temperatures:
For fixed installations: –40°C
For non-fixed (flexible) installations: –15°C
Minimum bending radius (as a multiple of cable outer diameter):
Unarmoured constructions: ≥ 6 × D
Armoured constructions: ≥ 12 × D
Packaging
Finished product + wooden barrel packaging

Technical index
|
Project |
General flame-retardant PVC |
Index |
|
|
Low smoke and low halogen PVC |
Low smoke halogen-free polyolefin |
||
|
Oxygen index% |
30-32 |
31-36 |
36-40 |
|
Smoke density ≤ |
600 |
300 |
Smoke 50, no flame 260 |
|
Hydrogen halide gas release maximum mg/g ≤ |
580 |
100 |
5 |
Main technical indicators of products
|
Project |
Technical index |
|
|||||||||||||||
|
DC resistance at 20℃ (MΩ.km ) |
Section |
0.5mm² |
0.75mm² |
1.0mm² |
1.5mm² |
2.5mm² |
4.0mm² |
6mm² |
10mm² |
||||||||
|
Cladding material |
Tin |
No-tin |
Tin |
No-tin |
Tin |
No-tin |
Tin |
No-tin |
Tin |
No-tin |
Tin |
No-tin |
Tin |
No-tin |
Tin |
No-tin |
|
|
Class A/B |
|
|
24.5 |
24.8 |
18.1 |
18.2 |
12.1 |
12.2 |
7.41 |
7.56 |
4.61 |
4.7 |
3.08 |
3.11 |
1.83 |
1.84 |
|
|
Class R |
39 |
40 |
26 |
26.7 |
19.5 |
20 |
13.3 |
13.7 |
7.98 |
8.21 |
|
|
|
|
|
|
|
|
Testing voltage |
3000V/5min |
||||||||||||||||
|
Insulation voltage |
Compliant with national standards |
||||||||||||||||
|
Flame retardant performance |
Complies with the national standard GB/T18380-2001 |
||||||||||||||||
Cross linking performance indicators
|
Project |
Unit |
Performance index |
Performance indicator |
|
Air temperature |
°C |
200 ±3 |
GB/T 2951.21-2008 |
|
Processing condition load time |
Min |
15 |
|
|
Mechanical stress |
N/cm2 |
20 |
|
|
Maximum elongation under load |
% |
175 |
|
|
Maximum permanent elongation after cooling |
% |
15 |

Hot Tags: pvc insulated control cable, China pvc insulated control cable manufacturers, suppliers, factory, Copper Tape Shielded Cable, Fire Resistant Control Cable, Flexible PVC Cable, Flexible Shielded Cable, Instrumentation And Control Cables, Sheathed Flexible Cable